1-717-217-2299 www.lumberg-automationusa.com10
LAN connection M12, D-Coded Power supply 7/8” Input/Output M12
1 = +24 V
2 = IN/OUT B
3 = GND (0 V)
4 = IN/OUT A
5 = earth
Housing = FE
1 = +24 V Actuators
2 = +24 V Logic / Sensors
3 = GND (0 V) Logic / Sensors
4 = GND (0 V) Actuators
Housing = FE
EtherNet/IP I/O Modules with 16 Digital Inputs and 16 Digital Outputs
0980 ESL 710
16 IN / 16 OUT (universal)
EtherNet/IP Device with 16 digital I/O channels,
channels can be used universally as inputs or
outputs, M12 socket, rotary address switches
for addressing, M12 LAN-Ports, D-coded, 7/8“
power supply.
Pin Assignment
1 = TD+
2 = RD+
3 = TD-
4 = RD
Housing = shielding
Bit Assignment
Bit
7 6 5 4 3 2 1 0
M12 Input
Byte 0
4B 4A 3B 3A 2B 2A 1B 1A
Byte 1
8B 8A 7B 7A 6B 6A 5B 5A
M12 Output
Byte 0
4B 4A 3B 3A 2B 2A 1B 1A
Byte 1
8B 8A 7B 7A 6B 6A 5B 5A
Diagnostic Indication
LED Indication Condition
1...8 A yellow channel status 1
1...8 DIA A red periphery fault
1... 8 B yellow channel status 2
1... 8 DIA B red periphery fault
U
S green
off
sensor power supply applied
sensor power supply missing
U
L green
off
actuator power supply applied
actuator power supply missing
P1 Lnk/Act green
yellow flashing
connected to an Ethernet device
I/O device exchanging data
P2 Lnk/Act green
yellow flashing
connected to an Ethernet device
I/O device exchanging data
MS
(Module status)
green
green flashing
red/green flashing
red flashing
off
device is ready for operating
wrong configuration
self test is running
firmware update
device is off
NS
(Network status)
green
green flashing
red
red flashing
off
connection to master exists
IP address exists, but no connection to the master
IP address is used by a different device
connection has timed out
device is off
Comentarios a estos manuales